Khởi động từ LP1K0910BD

Khởi động từ LP1K0910BD

đại lý LP1K0910BD | nhà phân phối LP1K0910BD | schneider LP1K0910BD

Thông số kỹ thuật contactor LP1K0910BD

Main
range of product
TeSys K
range
TeSys
product or component type
Contactor
product name
TeSys K
device short name
LP1K
device application
Control
contactor application
Motor control
Resistive load
Complementary
utilisation category
AC-1
AC-3
AC-4
poles description
3P
pole contact composition
3 NO
System Voltage
690 V AC 50/60 Hz power circuit
<= 690 V AC 50/60 Hz signalling circuit
[Ie] rated operational current
9 A at <= 440 V AC AC-3 power circuit
20 A (<= 122 °F (50 °C)) at <= 440 V AC AC-1 power circuit
16 A (<= 158 °F (70 °C)) at 690 V AC AC-1 power circuit
control circuit type
DC standard
[Uc] control circuit voltage
24 V DC
motor power kW
2.2 kW at 400 V AC 50/60 Hz AC-4
2.2 kW at 220…230 V AC 50/60 Hz AC-3
4 kW at 380…415 V AC 50/60 Hz AC-3
4 kW at 440 V AC 50/60 Hz AC-3
4 kW at 480 V AC 50/60 Hz AC-3
4 kW at 500…600 V AC 50/60 Hz AC-3
4 kW at 660…690 V AC 50/60 Hz AC-3
auxiliary contact composition
1 NO
[Uimp] rated impulse withstand voltage
8 kV
overvoltage category
III
[Ith] conventional free air thermal current
20 A at <= 122 °F (50 °C) power circuit
10 A at <= 122 °F (50 °C) signalling circuit
Irms rated making capacity
110 A AC power circuit conforming to NF C 63-110
110 A AC power circuit conforming to IEC 60947
110 A AC signalling circuit conforming to IEC 60947
rated breaking capacity
110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220…230 V conforming to IEC 60947
110 A at 380…400 V conforming to IEC 60947
70 A at 660…690 V conforming to IEC 60947
[Icw] rated short-time withstand current
20 A <= 50 °C >= 15 min power circuit
90 A <= 122 °F (50 °C) 1 s power circuit
85 A <= 122 °F (50 °C) 5 s power circuit
80 A <= 122 °F (50 °C) 10 s power circuit
60 A <= 122 °F (50 °C) 30 s power circuit
45 A <= 122 °F (50 °C) 1 min power circuit
40 A <= 122 °F (50 °C) 3 min power circuit
80 A 1 s signalling circuit
90 A 500 ms signalling circuit
110 A 100 ms signalling circuit
associated fuse rating
25 A gG at <= 440 V power circuit
25 A aM power circuit
10 A gG signalling circuit conforming to IEC 60947
10 A gG signalling circuit conforming to VDE 0660
average impedance
3 mOhm at 50 Hz – Ith 20 A power circuit
[Ui] rated insulation voltage
690 V signalling circuit conforming to IEC 60947-4-1
690 V signalling circuit conforming to IEC 60947-5-1
600 V signalling circuit conforming to UL 508
600 V power circuit conforming to CSA C22.2 No 14
600 V signalling circuit conforming to CSA C22.2 No 14
690 V power circuit conforming to IEC 60947-4-1
600 V power circuit conforming to UL 508
insulation resistance
> 10 MOhm signalling circuit
inrush power in W
3 W at 68 °F (20 °C)
hold-in power consumption in W
3 W at 68 °F (20 °C)
heat dissipation
3 W
control circuit voltage limits
0.8…1.15 Uc at <= 122 °F (50 °C) operational
0.1…0.75 Uc at <= 122 °F (50 °C) drop-out
connections – terminals
Screw clamp terminals 1 cable(s) 0…0.01 in² (1.5…4 mm²) – cable stiffness: solid
Screw clamp terminals 1 cable(s) 0…0.01 in² (0.75…4 mm²) – cable stiffness: flexible – without cable end
Screw clamp terminals 1 cable(s) 0…0 in² (0.34…2.5 mm²) – cable stiffness: flexible – with cable end
Screw clamp terminals 2 cable(s) 0…0.01 in² (1.5…4 mm²) – cable stiffness: solid
Screw clamp terminals 2 cable(s) 0…0.01 in² (0.75…4 mm²) – cable stiffness: flexible – without cable end
Screw clamp terminals 2 cable(s) 0…0 in² (0.34…1.5 mm²) – cable stiffness: flexible – with cable end
operating rate
3600 cyc/h
auxiliary contacts type
Type instantaneous (1 NO)
minimum switching current
5 mA signalling circuit
minimum switching voltage
17 V signalling circuit
mounting support
Plate
Rail
tightening torque
11.5 lbf.in (1.3 N.m) – on screw clamp terminals – with screwdriver Philips No 2
11.5 lbf.in (1.3 N.m) – on screw clamp terminals – with screwdriver flat Ø 6 mm
operating time
10 ms coil de-energisation and NO opening
30…40 ms coil energisation and NO closing
safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
non overlap distance
0.02 in (0.5 mm)
mechanical durability
10 Mcycles
electrical durability
0.18 Mcycles 20 A AC-1 at Ue <= 440 V
1.3 Mcycles 9 A AC-3 at Ue <= 440 V
mechanical robustness
Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27
Vibrations contactor closed 4 Gn, 5…300 Hz IEC 60068-2-6
Vibrations contactor opened 2 Gn, 5…300 Hz IEC 60068-2-6
Shocks contactor opened, on X axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Y axis 6 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on X axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Y axis 10 Gn for 11 ms IEC 60068-2-27
height
2.28 in (58 mm)
width
1.77 in (45 mm)
depth
2.24 in (57 mm)
product weight
0.5 lb(US) (0.225 kg)
compatibility code
LP1K
Environment
standards
BS 5424
IEC 60947
NF C 63-110
VDE 0660
product certifications
CSA
UL
IP degree of protection
IP2x conforming to VDE 0106
protective treatment
TC conforming to IEC 60068
TC conforming to DIN 50016
ambient air temperature for operation
-13…122 °F (-25…50 °C)
ambient air temperature for storage
-58…176 °F (-50…80 °C)
operating altitude
6561.68 ft (2000 m) without derating in temperature
flame retardance
V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
Ordering and shipping details
Category
22321 – CTR,K-LINE,DC,OPEN,NONREV
Discount Schedule
I12
GTIN
00785901832485
Nbr. of units in pkg.
1
Package weight(Lbs)
0.48999999999999999
Returnability
Y
Country of origin
FR
Offer Sustainability
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Compliant  – since  0633  –  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Product environmental profile
Available
Product end of life instructions
Available

Trả lời